Medium voltage cables with XLPE insulation and a concentric copper screen, ideal for distribution networks. Suitable for use in buildings, power stations, open air, underground, cable trays, and ducts where the risk of mechanical damage is low. These cables ensure reliable power transmission across a wide range of environmental conditions.
 
The structure includes aluminum or copper conductors (Class 2 - RMC) as per EN 60228, semi-conducting XLPE conductor and insulation screens, and XLPE insulation. A semiconducting nonwoven tape acts as inner covering beneath the helically applied copper wires and tape screen. Polyester tape and a red PVC outer sheath complete the build. Rated 18/30 kV, tested at 63 kV, withstanding operating temperatures up to +90 °C and short-circuit conditions up to +250 °C. Sizes range from 50/16 to 1000/50 mm², single-core.

0.00 KES

YHAKXS, YHKXS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 18/30 kV
YHAKXS, YHKXS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: PVC sheath (red color).
Parameters 
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -5
Frequency, Hz 50
Testing voltage, kV 63
Rated voltage, kV 18/30
Al Cu
Number of conductors 1
Minimum conductor size, mm 50/16
Maximum conductor size, mm 1000/50

 