YHAKXS and YHKXS are medium-voltage power cables designed for 8.7/15 kV distribution systems in buildings, power stations, ducts, trays, and open air, where mechanical stress is minimal. These cables use XLPE insulation and a concentric copper screen for reliable electrical performance and safety.
 
They feature stranded, round, compacted aluminum or copper conductors (EN 60228, Class 2), semi-conducting XLPE conductor and insulation screens, and XLPE insulation. Additional layers include a semiconducting nonwoven tape, helical copper wires and tape screen, polyester tape inner covering, and a red PVC outer sheath.
 
The cable operates in temperatures from –50 °C to +50 °C, with a maximum conductor temperature of +90 °C and a short-circuit limit of +250 °C. Rated at 8.7/15 kV and tested at 30.5 kV, it has a 15 × D bending radius. Available in single-core versions with sizes from 35 mm² to 1000 mm² (Al) or up to 50 mm² (Cu).

0.00 KES

YHAKXS, YHKXS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 8,7/15 kV
YHAKXS, YHKXS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: PVC sheath (red color).
Parameters 
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -5
Frequency, Hz 50
Testing voltage, kV 30,5
Rated voltage, kV 8,7/15
Cable Sizes
Al Cu
Number of conductors 1
Minimum conductor size, mm? 35/16
Maximum conductor size, mm? 1000/50