Power cables rated voltage 0.6/1 kV
YAKYFtly, YnAKYFtly (-J, -O), YKYFtly, YnKYFtly (-J, -O), HD 603, IEC 60502-1
Application Power cables suitable for laying in open air, in ground, in cable trays and ducts, in areas with high risk of
mechanical damage.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 1 - SE (solid, shaped),
Class 2 - RM (stranded, round), Class 2 - SM (stranded, shaped);
2. Insulation: PVC (color code acc. to HD 603 clause 4, -J - with Y/G core, -O - without Y/G core);
3. Filler/inner covering: PVC;
4. Armor: Galvanized steel tapes applied with overlap;
5. Cover: PVC sheath (black color), YnAKYFty, YnKYFty - PVC sheath (black color).
Parameters =
Exploitation temperature range,°C from -30 to 50
Short-circuit temperature,°C 160Bending radius 12D
Fire properties EN 60332-1; EN 60332-3-24 (for YnAKYFty, YnKYFty)
Operating conductor temperature°C max +70
Cabling (inside/outside) inside/outside
Installation temperature,°C 5
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 0,6/1
Cable sizes
AI | Cu | AI | Cu | AI | Cu | AI |Cu AI | Cu
Number of conductors 2 3 4 3+1 - 5
Minimum conductor size, mm 1 10 1 10 | 1 25+16 = 1
Maximum conductor size, mm 16 240 95 300 300+150 - 35