The YAKYFoy (aluminum) and YKYFoy (copper) cables are designed for medium-voltage power distribution in environments with increased mechanical risk, such as buildings, substations, underground routes, and cable trays. These cables are constructed with Class 2 stranded, shaped conductors (EN 60228), color-coded PVC insulation (HD 603), a concentric copper wire and tape screen, EPDM or plastic tape fillers, an inner PVC covering, and are armored with galvanized round steel wires. A final black PVC sheath ensures added durability and resistance.
 
Operating in temperatures from –50°C to +50°C and tolerating short-circuit temperatures up to +150°C, these 3-core cables are rated at 3.6/6 kV and tested at 12.5 kV. With fire resistance compliant to EN 60332-1-2 and a bending radius of 10 × D, they are suitable for both indoor and outdoor installation. Offered in conductor sizes ranging from 16 mm² to 300 mm², they provide safe and reliable power delivery for demanding applications.

0.00 KES

YAKYFoy, YKYFoy, IEC 60502-2

Additional product information

Power cables rated voltage 3,6/6 kV
YAKYFoy, YKYFoy, IEC 60502-2

Application Power cables for medium voltage distribution with PVC insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts, in areas with high risk of
mechanical damage.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - SM (stranded, shaped);
2. Insulation: PVC (color code acc. to HD 603);
3. Filler/inner covering: EPDM, plastic tape;
4. Screen: Copper wires and copper tape, applied helically;
5. Inner covering: PVC;
6. Armor: Galvanized round steel wires;
7. Cover: PVC sheath (black color).
Parameters 
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +150
Bending radius 10d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +70
Cabling (inside/outside) inside/outside
Installation temperature,°C min -5
Frequency, Hz 50
Testing voltage, kV 12,5
Rated vol kV '
Cable sizes 
Rated voltage, KV 3,6/6
A | Cu
Number of conductors 3
Minimum conductor size, mm 25 | 16
Maximum conductor size, mm 300

 