Low-voltage power cables rated 0.6/1 kV, compliant with HD 603 and IEC 60502-1, suitable for installation in buildings, power stations, open air, ground, ducts, and trays where no severe mechanical stress is expected. These cables feature aluminum (YAKY, YnAKY) or copper (YKY, YnKY) conductors per EN 60228 in solid (RE/SE) or stranded (RM/SM) form, insulated with PVC (HD 603 color code), with EPDM or plastic tape filler and a black PVC sheath. Fire-rated to EN 60332-1-2; YnAKY and YnKY versions also meet EN 60332-3-24. Designed for use between -30 °C and +50 °C, with a maximum conductor temperature of +70 °C and short-circuit limits of 160 °C (S ≤ 300 mm²) or 140 °C (S > 300 mm²). Supports 1 to 5 conductors, with sizes from 1 mm² to 630 mm². Bending radius is 15D for single-core and 12D for multi-core, installation temperature ≥5 °C, operating at 50 Hz and tested at 4 kV. A versatile, reliable solution for low-voltage power distribution.

0.00 KES

YAKY, YnAKY (-J, -O), YKY, YnKY (-J, -O), HD 603, IEC 60502-1

Additional product information

Power cables rated voltage 0.6/1 kV
YAKY, YnAKY (-J, -0), YKY, YnKY (-J, -O), HD 603, IEC 60502-1

Application Power cables suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 1 - SE (solid, shaped),
Class 2 - RM (stranded, round), Class 2 - SM (stranded, shaped);
2. Insulation: PVC (color code acc. to HD 603 clause 4, -] - with Y/G core, -O - without Y/G core);
3. Filler/inner covering: EPDM or plastic tape;
4. Cover: PVC sheath (black color), YnAKY, YnKY - PVC sheath (black color).
Parameters 
Exploitation temperature range,°C from -30 to 50
EN Short-circuit temperature,°C 160 (S<300mm’); 140 (S>300mm’)
Bending radius 15D (single core); 12D (multi core)
Fire properties EN 60332-1-2; EN 60332-3-24 (for YnAKY, YnKY)
Operating conductor temperature,°C max +70
Cabling (inside/outside) inside/outside
Installation temperature°C 5
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 0,6/1
Cable sizes 
Number of conductors 1 2 3 34+1 4 5
Minimum conductor size, mm? 10 | 1 - 1 10 | 1 25+16 10 1 1 | 1
Maximum conductor size, mm? 630 - 16 240 300+150 300 240 185

 