The YAKY (aluminum) and YKY (copper) multicore cables are designed for medium-voltage distribution in environments such as buildings, power stations, open air, ground, cable trays, and ducts where mechanical damage is not expected. Built to EN 60228 Class 2 standards, they feature stranded, shaped conductors, PVC insulation (HD 603), a filler layer of EPDM+PVC or tape, helically applied copper wire and tape screening, and a black PVC outer sheath.
 
Rated for 3.6/6 kV and tested at 12.5 kV, these cables perform in temperatures from –50°C to +50°C, withstanding short-circuit heat up to +150°C. Fire-rated to EN 60332-1-2, they support both indoor and outdoor use at 50 Hz. Available in 3-core configurations, they come in sizes from 16 mm² to 300 mm², with a bending radius of 10 × D.

0.00 KES

YAKY, YKY (Multicore), IEC 60502-2

Additional product information

Power cables rated voltage 3,6/6 kV
YAKY, YKY, multicore, IEC 60502-2

Application Power cables for medium voltage distribution with PVC insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - SM (stranded, shaped);
2. Insulation: PVC (color code acc. to HD 603);
3. Filler/inner covering: EPDM+PVC, PVC or plastic tape;
4. Screen: Copper wires and copper tape, applied helically;
5. Cover: PVC sheath (black color).
Parameters
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +150
Bending radius 10d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +70
Cabling (inside/outside) inside/outside
Installation temperature,°C min -5
Frequency, Hz 50
Testing voltage, kV 12,5
Rated Voltage, kV 3,6/6
Cable sizes 
AI Cu
Number of conductors 3
Minimum conductor size, mm? 25/16 | 16/16
Maximum conductor size, mm? 300/50

 