Low-voltage power cables rated 0.6/1 kV, compliant with HD 603 and IEC 60502-1, suitable for fixed installations in buildings, power stations, in open air, underground, ducts, and trays where mechanical protection is not critical. These cables are built with aluminum (YAKXS, YnAKXS) or copper (YKXS, YnKXS) conductors per EN 60228 in solid (RE/SE) or stranded (RM/SM) forms. They are insulated with XLPE (HD 603 color code), filled with EPDM or plastic tape, and covered with a black PVC sheath. The YnAKXS and YnKXS variants are also fire-rated to EN 60332-3-24. Operating in temperatures from -30 °C to +50 °C, with a max conductor temperature of +90 °C and short-circuit tolerance up to 250 °C. These cables allow a bending radius of 15D (single-core) and 12D (multi-core), can be installed from +5 °C, operate at 50 Hz, and are tested at 4 kV. They are offered in 1 to 5 conductor versions, with conductor sizes ranging from 1 mm² to 500 mm².

0.00 KES

YAKXS, YnAKXS (-J, -O), YKXS, YnKXS (-J, -O), HD 603, IEC 60502-1

Additional product information

Power cables rated voltage 0.6/1 kV
YAKXS, YnAKXS (-J, -O), YKXS, YnKXS (-J, -O), HD 603, IEC 60502-1

Application Power cables suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 1 - SE (solid, shaped),
Class 2 - RM (stranded, round), Class 2 - SM (stranded, shaped);
2. Insulation: XLPE (color code acc. to HD 603 clause 4, -J - with Y/G core, -O - without Y/G core);
3. Filler/inner covering: EPDM or plastic tape;
4. Cover: PVC sheath (black color), YnAKXS, YnKXS - PVC sheath (black color).
Parameters
Exploitation temperature range,°C from -30 to 50
Short-circuit temperature,°C 250
Bending radius 15D (single core); 12D (multi core)
Fire properties EN 60332-1; EN 60332-3-24 (for YnAKXS, YnKXS)
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C 35}
Frequency, Hz 50
Rated voltage, kV 0,6/1
Cable sizes 
AI | Cu AI| Cu | AI Cu | AI | Cu | AI | Cu AI | Cu
Number of conductors 1 2 3 4 5
Minimum conductor size, mm 10 1  1  1 25  1 16 1
Maximum conductor size, mm 500 16 240 240 185

 