Medium voltage distribution cables featuring XLPE insulation, a concentric copper screen, and longitudinal water sealing. Designed for use in power stations, buildings, open air, underground, ducts, and cable trays where mechanical damage is not expected. These cables provide stable, long-term performance in various environments.
 
Constructed with Class 2 aluminum or copper conductors per EN 60228, these cables include semi-conducting XLPE screens, XLPE insulation, and water-swellable tapes for moisture protection. A helically applied copper wire screen ensures shielding, while a robust black PE sheath offers resistance to weather. They operate up to +90 °C, handle short-circuits up to +250 °C, and are rated 18/30 kV with testing at 63 kV. Sizes range from 50/16 to 1000/50 mm².

0.00 KES

XUHAKXS, XUHKXS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 18/30 kV
XUHAKXS, XUHKXS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen and longitudinal
sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Non-conducting water-swellable tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 63
Rated voltage, kV 18/30
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 50/16
Maximum conductor size, mm 1000/50