Medium voltage distribution cables with XLPE insulation, concentric copper screen, and longitudinal water sealing. Suitable for indoor and outdoor installation in buildings, power stations, underground, ducts, trays, and open air, provided no excessive mechanical damage is expected.
 
The cable features aluminum or copper conductors per EN 60228 (Class 2), semi-conducting XLPE conductor and insulation screens, and XLPE insulation. Inner layers include semiconducting and non-conducting water-swellable tapes. The screen comprises helically applied copper wires and tape, finished with a black weather-resistant PE sheath. Rated at 12/20 kV with 50 Hz frequency, it has a max conductor temperature of +90°C, a short-circuit temp of +250°C, and operates from -60°C to +50°C. Minimum installation temp is -20°C. Bending radius: 15d. Testing voltage: 42 kV. Available in single-conductor versions with sizes from 35 mm² to 1000 mm² (Al) or 16 mm² to 50 mm² (Cu).

0.00 KES

XUHAKXS, XUHKXS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12/20 kV
XUHAKXS, XUHKXS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen and longitudinal
sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Non-conducting water-swellable tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties .
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 42
Rated voltage, kV 12/20
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 1000/50

 

info@belken-power.com