XUHAKXS and XUHKXS are medium-voltage power cables designed for distribution in buildings, power stations, and outdoor or underground installations where mechanical damage is unlikely. These cables feature XLPE insulation, a concentric copper screen, and longitudinal water sealing for added protection.
 
They are made with stranded Class 2 aluminum (XUHAKXS) or copper (XUHKXS) conductors (EN 60228), semi-conducting XLPE conductor and insulation screens, and a water-swellable tape for longitudinal sealing. A copper wire and tape screen, additional non-conducting water-swellable layer, and a black PE outer sheath enhance durability.
 
The cables operate between –60 °C and +50 °C, support conductor temperatures up to +90 °C, and withstand short-circuit temps of +250 °C. Rated at 8.7/15 kV with 30.5 kV testing voltage, they are suitable for 50 Hz systems and require a bending radius of 15 × D. Available in 1-core, 35–1000 mm² (Al) and up to 50 mm² (Cu).

0.00 KES

XUHAKXS, XUHKXS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 8,7/15 kV
XUHAKXS, XUHKXS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen and longitudinal
sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Non-conducting water-swellable tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties -
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 30,5
Rated voltage, kV 8,7/15
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 1000/50

 