These medium-voltage power cables are designed for distribution networks, featuring XLPE insulation, a concentric copper screen, and both longitudinal and radial sealing for enhanced moisture resistance. Suitable for installation in buildings, substations, cable trays, ducts, underground, or in open air—where risk of mechanical damage is low. Variants with the “n” index offer improved flame retardant performance.
 
They are built with aluminum or copper conductors (EN 60228, Class 2), semi-conductive XLPE screening, and water-swellable tapes for internal sealing. The radial barrier uses an aluminum/plastic laminate bonded to a weather-resistant PE sheath—black for standard types and red for “n” versions. Rated 18/30 kV, they operate up to +90 °C, withstand short circuits at +250 °C, and are tested at 63 kV. Sizes range from 50/16 to 1000/50 mm².

0.00 KES

XRUHAKXS, XnRUHAKXS, XRUHKXS, XnRUHKXS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 18/30 kV
XRUHAKXS, XnRUHAKXS, XRUHKXS, XnRUHKXS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen, longitudinal and
radial sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected. "n" - increased flame retardance properties.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE. For cables with index "n" - weather-resistant PE (red color).
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2 for cables with index «n>»
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 63
Rated voltage, kV 18/30
Cable Sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 50/16
Maximum conductor size, mm 1000/50

 