These medium-voltage power cables are designed for reliable energy distribution in buildings, power stations, outdoors, or underground where mechanical stress is minimal. They feature XLPE insulation, concentric copper screening, and both longitudinal and radial water sealing. The "n" variants offer enhanced flame retardance (EN 60332-1-2) and are sheathed in red weather-resistant PE.
 
Cables include stranded aluminum (XRUHAKXS, XnRUHAKXS) or copper (XRUHKXS, XnRUHKXS) conductors (EN 60228, Class 2), with semi-conducting XLPE conductor and insulation screens. A semiconducting water-swellable tape ensures longitudinal sealing, while a radial barrier of aluminum/plastic laminate provides additional moisture protection. Operating from –60 °C to +50 °C, these cables handle +90 °C during operation and +250 °C under short-circuit conditions. Rated at 8.7/15 kV with 30.5 kV test voltage, suitable for 50 Hz, and available in single-core sizes from 35 mm² to 1000 mm² (Al) and up to 50 mm² (Cu).

0.00 KES

XRUHAKXS, XnRUHAKXS, XRUHKXS, XnRUHKXS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 8,7/15 kV
XRUHAKXS, XnRUHAKXS, XRUHKXS, XnRUHKXS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen, longitudinal and
radial sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected. "n" - increased flame retardance properties.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE. For cables with index "n" - weather-resistant PE (red color).
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2 (for cables with index «n>>)
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 30,5
:Rated voltage, kV 87/15
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 1000/50

info@belken-power.com