XRUHAKXS (aluminum) and XRUHKXS (copper) are single-core medium-voltage cables with XLPE insulation, a concentric copper screen, and both longitudinal and radial water sealing. The "n" versions offer enhanced flame retardance. Suitable for installation in buildings, power stations, open air, ground, cable trays, and ducts where mechanical damage is not expected.
 
These cables use Class 2 compacted conductors (EN 60228), semi-conducting XLPE layers, water-swellable tapes, a helically applied copper screen, an aluminum/plastic laminate radial barrier, and a weather-resistant PE sheath (black or red for “n”). Rated 6/10 kV and tested at 21 kV, they operate from –60°C to +50°C, withstand +250°C short-circuit temperatures, and support conductor temperatures up to +90°C. Minimum installation temperature is –20°C, with a bending radius of 15 × D. Sizes range from 25 mm² to 1000 mm² (Al) and 16 mm² to 35 mm² (Cu).

0.00 KES

XRUHAKXS, XnRUHAKXS, XRUHKXS, XnRUHKXS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
XRUHAKXS, XnRUHAKXS, XRUHKXS, XnRUHKXS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen, longitudinal and
radial sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected. "n" - increased flame retardance properties.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE. For cables with index "n" - weather-resistant PE (red color).
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2 for cables with index «n»
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21

Rated voItage, kV 6/10
A | G
Number of conductors 1
Minimum conductor size, mm 50/16 | 25/16
Maximum conductor size, mm 1000/35

 