Additional product information
Power cables rated voltage 6/10 kV
XRUHAKXS, XnRUHAKXS, XRUHKXS, XnRUHKXS, HD 620, IEC 60502-2
Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen, longitudinal and
radial sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected. "n" - increased flame retardance properties.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE. For cables with index "n" - weather-resistant PE (red color).
Parameters
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2 for cables with index «n»
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21
Rated voItage, kV 6/10
A | G
Number of conductors 1
Minimum conductor size, mm 50/16 | 25/16
Maximum conductor size, mm 1000/35
info@belken-power.com