Power cables rated 0.6/1 kV, designed for use in buildings, power stations, outdoors, direct burial in ground, cable trays, and ducts—ideal where mechanical damage is not expected. Also suitable for plough cabling. Constructed with copper conductors per EN 60228, available in Class 2 RM (stranded round) and FLEX type (annealed cores). Insulated with XLPE (HD 603 color-coded) and sheathed in black PVC or weather-resistant black PE (for XMK-PE versions).
 
The operating temperature range is -30°C to +50°C, with a maximum conductor temperature of +90°C and short-circuit tolerance up to 250°C. Supports a bending radius of 15D, is fire-rated to EN 60332-1-2 (for PVC-sheathed variants), and tested at 4 kV. Suitable for both indoor and outdoor cabling, with a minimum installation temperature of -15°C and standard operating frequency of 50 Hz. Available as single-core cables with copper conductor sizes ranging from 35 mm² to 800 mm².

0.00 KES

XMK, XMK-PE, IEC 60502-1, HD 603-5D

Additional product information

Power cables rated voltage 0.6/1 kV
XMK, XMK-PE, SFS 4879, HD 603, IEC 60502-1

Application Power cables suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected. Suitable for plough cabling.
Construction 1. Conductor: Copper acc. to EN 60228, Class 2 - RM (stranded, round), FLEX - for annealed cores;
2. Insulation: XLPE (color code acc. to HD 603 clause 4);
3. Cover: PVC sheath (black color). Weather-resistant black color PE (for XMK-PE).
Parameters
Exploitation temperature range,°C from -30 to 50
Short-circuit temperature,°C 250
Bending radius 15D
Fire properties EN 60332-1-2 (for cable with PVC sheath)
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C -15
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 6/1
Cable sizes 
Number of conductors 1
Minimum conductor size, mm? 35
Maximum conductor size, mm? 800

 