Installation cable XMJ compliant with SFS 2091 and EVS 720, engineered for indoor and outdoor use where direct burial is not applicable. Constructed with copper conductors per EN 60228—solid (Class 1 RE) for 1.5–2.5 mm² and stranded (Class 2 RM) for 4–25 mm²—this cable features XLPE insulation (color-coded to HD 308), EPDM filler, and a white PVC outer sheath. Rated for 300/500 V and 450/750 V systems, XMJ supports 2 to 5 conductors and operates efficiently at 50 Hz. Designed for environments ranging from -50 °C to +50 °C, with a short-circuit endurance of 250 °C and a max conductor temperature of +90 °C, this cable offers enhanced thermal resistance. Compliant with EN 60332-1-2 for fire safety, it features a 12D bending radius, -15 °C installation temperature, and 2.5 kV test voltage, making it a robust choice for versatile power distribution applications.

0.00 KES

XMJ, SFS 2091; EVS 720

Additional product information

Installation cables
XMJ, SFS 2091; EVS 720

Application For indoor and outdoor installation. Unfit for laying in ground.
Construction 1. Conductor: Copper acc. to EN 60228. Class 1 - RE (solid, round), Class 2 - RM (round, stranded);
2. Insulation: XLPE (color code acc. to HD 308);
3. Filling: EPDM;
4. Sheath: PVC (white color).
Parameters 
$ Exploitation temperature range,°C from -50 up to 50
AS Short-circuit temperature,°C 250
& Bending radius 12D
ot'y Fire properties EN 60332-1-2
©} Operating conductor temperature,°C max +90
Bs Cabling (inside/outside) inside/outside
‘ Installation temperature,°C =15
HH] Frequency, Hz 50
Testing voltage, kV 2,5
Rated voltage, kV 300/500V, 450/750V
Wire sizes
Number of conductors 2-5
Cross-section of conductors, mm (conductor type):
XMJ 300/500 V 1.5 - 2.5 (RE)
XMJ 450/750 V 4-25 (RM)

info@belken-power.com