Medium voltage cables with XLPE insulation and a concentric copper screen, suitable for indoor/outdoor use in buildings, power stations, cable trays, ducts, or ground, where mechanical damage is unlikely. The conductor (Al or Cu) complies with EN 60228, Class 2 (stranded, round, compacted). Layers include semi-conductive XLPE screens, XLPE insulation, semiconducting nonwoven and polyester tapes, copper wires and tape screen, and a black weather-resistant PE sheath.
 
Operating temp: –60°C to +50°C. Max conductor temp: +90°C. Short-circuit temp: +250°C. Install temp: –20°C min. Bending radius: 15× cable diameter. Rated voltage: 12/20 kV. Test voltage: 42 kV. Frequency: 50 Hz. Available in 1-core, sizes 35–1000 mm² (Al), 16–50 mm² (Cu).

0.00 KES

XHAKXS, XHKXS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12/20 kV
XHAKXS, XHKXS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties S
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 42
Rated voltage, kV 12/20
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 1000/50

 