Additional product information
Power cables rated voltage 0.6/1 kV
NAYRGY (-J, -O), NYRGY (-J, -0), DIN VDE 0276-603, HD 603, IEC 60502-1
Application Power cables suitable for laying in open air, in ground, in cable trays and ducts, in areas with high risk of
mechanical damage.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 1 - SE (solid, shaped),
Class 2 - RM (stranded, round), Class 2 - SM (stranded, shaped);
2. Insulation: PVC (color code acc. to HD 603 clause 4, -J - with Y/G core, -O - without Y/G core);
3. Filler/inner covering: PVC;
4. Armor: Galvanized round steel wires;
5. Cover: PVC sheath (black color).
Parameters
Exploitation temperature range,°C from -50 to 50
Short-circuit temperature,°C 160
Bending radius 12D
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +70
Cabling (inside/outside) inside/outside
Installation temperature,°C =5
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 0,6/1
Cable sizes
AI Cu AI Cu AI Cu AI Cu AI Cu
Number of conductors 2 3 3+1 4 5
Minimum conductor size, mm 25 | 15 6 | 15 25+16 | 35+16 6 10 6 1,5
Maximum conductor size, mm 35 240 240+120 240 300 25 70