Power cables rated 0.6/1 kV, compliant with DIN VDE 0276-603, HD 603, and IEC 60502-1, designed for fixed installations in buildings, power stations, in open air, ground, cable trays, and ducts where mechanical damage is not expected. Built with aluminum (NA2XY) or copper (N2XY) conductors per EN 60228 in solid (RE/SE) or stranded (RM/SM) form, insulated with XLPE (HD 603 color-coded), filled with EPDM, and protected by a black PVC sheath. These cables operate between -50 °C and +50 °C, withstand short-circuit temperatures up to 250 °C, and support a maximum conductor temperature of +90 °C. They maintain a bending radius of 15D (single-core) or 12D (multi-core), install at temperatures from +5 °C, operate at 50 Hz, and are tested at 4 kV. Available in 1 to 4-core versions with conductor sizes ranging from 16 mm² to 500 mm², and fire-rated according to EN 60332-1-2.

0.00 KES

NA2XY (-J, -O), N2XY (-J, -O), DIN VDE 0276-603, HD 603, IEC 60502-1

Additional product information

Power cables rated voltage 0.6/1 kV
NA2XY (-J, -O), N2XY (-J, -O), DIN VDE 0276-603, HD 603, IEC 60502-1

Application Power cables suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 1 - SE (solid, shaped),
Class 2 - RM (stranded, round), Class 2 - SM (stranded, shaped);
2. Insulation: XLPE (color code acc. to HD 603 clause 4, -) - with Y/G core, -O - without Y/G core);
3. Filler/inner covering: EPDM;
4. Cover: PVC sheath (black color).
Parameters
Exploitation temperature range,°C from -50 to 50
Short-circuit temperature,°C 250
Bending radius 15D (single core); 12D (multi core)
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C =5
Frequency, Hz 50
Testing voltage, kV 4
Rated VoItage, kV 0,6/1
Cable sizes 
AI Cu AI Cu
Number of conductors 1 4
Minimum conductor size, mm? 50 25 16
Maximum conductor size, mm? 500 240 185

 