Medium voltage power cables designed for reliable energy distribution in utility and industrial networks. Featuring XLPE insulation and a concentric copper screen, these cables ensure high thermal and electrical performance. Suitable for installation in buildings, substations, open air, underground, cable trays, and ducts where low mechanical risk is expected. Their construction offers good resistance to moisture, heat, and aging for long service life.
 
The cable consists of a Class 2 aluminum or copper conductor (EN 60228), semi-conducting conductor screen, XLPE insulation, and semi-conductive insulation screen. It includes a semiconducting nonwoven tape, copper wires and tape screen applied helically, polyester tape, and a red PVC sheath. Rated voltage: 12/20 kV; test voltage: 42 kV; max operating temp: +90 °C; short-circuit temp: +250 °C; min install temp: -5 °C; bending radius: 15×D. Sizes range from 50–1000 mm² (Al) and 35–35 mm² (Cu). Fire performance: EN 60332-1-2.

0.00 KES

NA2XSY, N2XSY, VDE 0276-620, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12/20 kV
NA2XSY, N2XSY, VDE 0276-620, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: PVC sheath (red color).
Parameters 
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -5
Frequency, Hz 50
Testing voltage, kV 42 
Rated voltage, kV 12/20
Cable sizes 
AI Cu
Number of conductors 1
Minimum conductor size, mm? 50/16 | 35/16
Maximum conductor size, mm? 1000/35