NA2XS2Y (aluminum) and N2XS2Y (copper) are single-core medium-voltage cables designed for power distribution in environments with low mechanical stress. They are suitable for use in buildings, substations, open air, underground, cable trays, and ducts. These cables are constructed with Class 2 stranded, compacted conductors (EN 60228), XLPE insulation, semi-conducting XLPE screens, semiconducting nonwoven tape, polyester tape, helically applied copper screen, and a weather-resistant black PE sheath.
 
Rated 6/10 kV and tested at 21 kV, they operate from –60°C to +50°C, withstand short-circuit temperatures up to +250°C, and support a conductor temperature of +90°C. Designed for 50 Hz systems, they allow installation from –20°C with a bending radius of 15 × D. Available in sizes from 50 mm² to 1000 mm² (Al) and 25 mm² to 35 mm² (Cu).

0.00 KES

NA2XS2Y, N2XS2Y, VDE 0276-620, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
NA2XS2Y, N2XS2Y, VDE 0276-620, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties -
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10
Cable sizes 
AI Cu
Number of conductors 1
Minimum conductor size, mm 50/16 | 25/16
Maximum conductor size, mm 1000/35