These high-performance medium-voltage cables are engineered for power distribution networks where both radial and longitudinal water sealing is essential. With XLPE insulation and a copper concentric screen, they are ideal for indoor and outdoor installations in buildings, power stations, cable trays, ducts, and underground locations where mechanical damage is not expected.
 
The cable structure includes Class 2 aluminum or copper conductors per EN 60228, semi-conductive XLPE layers, water-swellable tapes for longitudinal sealing, and a radial barrier using aluminum/plastic laminate bonded to a black PE outer sheath. The screen comprises helically applied copper wires and tape. Designed for a rated voltage of 18/30 kV and tested at 63 kV, these cables perform at up to +90 °C in operation and +250 °C during short circuits, with conductor sizes from 50/16 mm² to 1000/35 mm².

0.00 KES

NA2XS(FL)2Y, N2XS(FL)2Y, VDE 0276-620, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 18/30 kV
NA2XS(FL)2Y, N2XS(FL)2Y, VDE 0276-620, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen, longitudinal and
radial sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 63
Rated voltage, kV 18/30
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 50/16
Maximum conductor size, mm 1000/35