Additional product information
Power cables rated voltage 6/10 kV
NA2XS(FL)2Y, N2XS(FL)2Y, VDE 0276-620, HD 620, IEC 60502-2
Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen, longitudinal and
radial sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE.
Parameters
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties .
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10
Cable sizes
AI Cu
Number of conductors 1
Minimum conductor size, mm 50/16 | 25/16
Maximum conductor size, mm 1000/35