These medium-voltage cables are designed for distribution networks requiring high reliability and protection from moisture ingress. Featuring XLPE insulation, a concentric copper screen, and longitudinal water-swellable sealing tapes, they are suitable for use in power stations, buildings, open air, cable trays, ducts, and direct burial where minimal mechanical stress is expected.
 
The cable consists of aluminum or copper Class 2 conductors (EN 60228), semi-conducting XLPE layers over the conductor and insulation, and a helically applied copper wire and tape screen. Water-swellable tapes enhance sealing around both the conductor and the screen. A weather-resistant black PE outer sheath ensures durability in harsh conditions. Rated 18/30 kV, they withstand 63 kV testing, operate at up to +90 °C, and tolerate short circuits up to +250 °C. Sizes range from 50/16 to 1000/35 mm².

0.00 KES

NA2XS(F)2Y, N2XS(F)2Y, VDE 0276-620, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 18/30 kV
NA2XS(F)2Y, N2XS(F)2Y, VDE 0276-620, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen and longitudinal
sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Non-conducting water-swellable tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 63
Rated voltage, kV 18/30
Cable sizes :
Al Cu
Number of conductors 1
Minimum conductor size, mm 50/16
Maximum conductor size, mm 1000/35

info@belken-power.com