Medium voltage distribution cables with XLPE insulation, concentric copper screen, and longitudinal water sealing. Suitable for fixed indoor/outdoor use in buildings, power stations, open air, underground, ducts, and trays where mechanical damage is not expected. These cables are designed for durability, moisture resistance, and long service life in demanding environments.
 
Construction includes stranded aluminum or copper conductor (EN 60228, Class 2), semiconducting conductor screen, XLPE insulation, semiconducting insulation screen, and water-swellable layers. A copper wire and tape screen provides shielding, covered by a black PE sheath. Rated 12/20 kV; operating temp: +90°C; short-circuit temp: +250°C; min install temp: -20°C; bending radius: 15×D; frequency: 50 Hz; test voltage: 42 kV. Conductor sizes: 35/16 to 1000/35 mm².

0.00 KES

NA2XS(F)2Y, N2XS(F)2Y, VDE 0276-620, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12/20 kV
NA2XS(FL)2Y, N2XS(FL)2Y, VDE 0276-620, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen, longitudinal and
radial sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 42
Rated voltage, kV 12/20
Cable sizes 
AI Cu
Number of conductors 1
Minimum conductor size, mm 50/16 | 35/16
Maximum conductor size, mm 1000/35

 