Medium voltage distribution cables with XLPE insulation, concentric copper screen, and longitudinal water sealing. Suitable for indoor/outdoor use in buildings, power stations, open air, underground, ducts, and trays where mechanical damage is not expected.
 
Construction: Stranded aluminum or copper conductor (EN 60228, Class 2), semiconducting XLPE conductor screen, XLPE insulation, semiconducting insulation screen, water-swellable semiconducting and non-conducting tapes, copper wires and tape screen, and a weather-resistant black PE sheath.
Rated 12/20 kV; operating temp: +90°C; short-circuit temp: +250°C; min install temp: -20°C; bending radius: 15×D; frequency: 50 Hz; test voltage: 42 kV. Conductor sizes: 35/16 to 1000/35 mm².

0.00 KES

NA2XS(F)2Y, N2XS(F)2Y, VDE 0276-620, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12/20 kV
NA2XS(F)2Y, N2XS(F)2Y, VDE 0276-620, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen and longitudinal
sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Non-conducting water-swellable tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 42 
Rated voltage, kV 12/20
Cable sizes 
AI Cu
Number of conductors 1
Minimum conductor size, mm 50/16 | 35/16
Maximum conductor size, mm 1000/35