Power cables rated voltage 0.6/1 kV
NA2X2Y (-J, -O), N2X2Y (-J, -O), DIN VDE 0276-603, HD 603, IEC 60502-1
Application Power cables suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 1 - SE (solid, shaped),
Class 2 - RM (stranded, round), Class 2 - SM (stranded, shaped);
2. Insulation: XLPE (color code acc. to HD 603 clause 4, -J - with Y/G core, -O - without Y/G core);
3. Filler/inner covering: EPDM;
4. Cover: Weather-resistant black color PE.
Parameters
Exploitation temperature range,°C from -50 to 50
Short-circuit temperature,°C 250
Bending radius 15D (single core); 12D (multi core)
Fire properties
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C -20
Frequency, Hz 50
Testing voltage, kV 4
Cable sizes
AI Cu AI Cu
Number of conductors 1 4
Minimum conductor size, mm 50 25 16
Maximum conductor size, mm 500 240 185