Medium voltage XLPE-insulated power cables designed for efficient energy distribution. Suitable for installation in buildings, outdoors, underground, ducts, trays, and wet locations where mechanical stress is minimal. These cables are ideal for modern power infrastructure that requires durability and moisture protection.
 
Constructed with Class 2 water-tight aluminum conductors (EN 60228), semi-conductive XLPE layers, and semiconducting water-swellable tapes for internal protection. A copper wire and tape screen is helically applied, with an aluminum/plastic laminate radial water barrier and a black weather-resistant PE sheath. Rated 20.8/36 kV, tested at 83.2 kV, with sizes from 50/16 mm² to 240/35 mm². Operating temp up to +90 °C, short-circuit temp +250 °C, and bending radius 15×D.

0.00 KES

EAXeCeWB, HD 620-10B, IEC 60502-2

Additional product information

Power cables rated voltage 20,8/36 (42) kV
EAXeCeWB, HD 620-10B, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation. Suitable for laying in buildings, in open air, in
ground, in cable trays and ducts where mechanical damage is not expected, in wet locations.
Construction 1. Conductor: Aluminum acc. to EN 60228 (water tight). Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 up to 50
Short-circuit temperature,°C 250
Bending radius 15D
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C -20
Frequency, Hz 50
Testing voltage, kV 83,2
Rated voltage, kV 20,8/36
Cable sizes 
Number of conductors 1
Minimum conductor size, mm 50/16
Maximum conductor size, mm 240/35

 