Power cables rated 0.6/1 kV, designed in compliance with HD 603-3A and IEC 60502-1, suitable for single cable line installations in cable structures and premises. Fire protection is required in group installations. These cables can be laid without restrictions on elevation, including vertical sections. Constructed with aluminum (E-AY2Y) or copper (E-Y2Y) conductors per EN 60228 in solid or stranded form, with PVC insulation (HD 603 color-coded), polypropylene cords or EPDM/plastic tape fillers, and a weather-resistant black PE sheath. They operate from -50 °C to +50 °C, with a max conductor temperature of +70 °C and short-circuit ratings of 160 °C (≤300 mm²) or 140 °C (>300 mm²). Bending radius is 15D (single-core) and 12D (multi-core), installation from -20 °C, operating at 50 Hz and tested at 4 kV. Available in 1 to 5-core versions with conductor sizes from 1.5 mm² to 630 mm².

0.00 KES

E-AY2Y, E-Y2Y, HD 603-3A, IEC 60502-1

Additional product information

Power cables rated voltage 0.6/1 kV
E-AY2Y, E-Y2Y, HD 603-3A, IEC 60502-1

Application The cables are designed for single cable lines laying in cable structures and premises. It is required to use fire
protection means in case of group laying. The cables can be laid without restriction on difference in levels along
the laying route including laying on vertical sections of the route.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 1 - SE (solid, shaped),
Class 2 - RM (stranded, round), Class 2 - SM (stranded, shaped);
2. Insulation: PVC (color code acc. to HD 603 clause 4, -J - with Y/G core, -O - without Y/G core);
3. Filler/inner covering: polypropylene cords/ EPDM or plastic tape;
4. Cover: Weather-resistant black color PE.
Parameters —
Exploitation temperature range,°C from -50 up to 50
Short-circuit temperature,°C
S < 300 mm2 160
S > 300 mm2 140
Bending radius
single core 15D
multi core 12D
Fire properties
Operating conductor temperature,°C max +70
Cabling (inside/outside) inside/outside
Installation temperature,°C -20
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 0,6/1
Cable sizes 
AI Cu  AI Cu AI Cu AI Cu AI Cu
Number of conductors 1 2 3 4 5
Minimum conductor size, mm? 25 16 1,5 25  1,5 25 1,5 25 16
Maximum conductor size, mm? 630 - 16 400 400 240

 