Additional product information
Power cables rated voltage 0.6/1 kV
E-AY2Y, E-Y2Y, HD 603-3A, IEC 60502-1
Application The cables are designed for single cable lines laying in cable structures and premises. It is required to use fire
protection means in case of group laying. The cables can be laid without restriction on difference in levels along
the laying route including laying on vertical sections of the route.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 1 - SE (solid, shaped),
Class 2 - RM (stranded, round), Class 2 - SM (stranded, shaped);
2. Insulation: PVC (color code acc. to HD 603 clause 4, -J - with Y/G core, -O - without Y/G core);
3. Filler/inner covering: polypropylene cords/ EPDM or plastic tape;
4. Cover: Weather-resistant black color PE.
Parameters —
Exploitation temperature range,°C from -50 up to 50
Short-circuit temperature,°C
S < 300 mm2 160
S > 300 mm2 140
Bending radius
single core 15D
multi core 12D
Fire properties
Operating conductor temperature,°C max +70
Cabling (inside/outside) inside/outside
Installation temperature,°C -20
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 0,6/1
Cable sizes
AI Cu AI Cu AI Cu AI Cu AI Cu
Number of conductors 1 2 3 4 5
Minimum conductor size, mm? 25 16 1,5 25 1,5 25 1,5 25 16
Maximum conductor size, mm? 630 - 16 400 400 240
info@belken-power.com