Additional product information
Wires for overhead power transmission lines
CCSX-WK, EN 50397-1
Application For overhead power transmission lines.
Construction 1. Conductor: Aluminum alloy, type AL3 acc. to EN 50183, RM (stranded, round, compacted), watertight;
2. Conductor screen: Conducting XLPE;
3. Insulation: XLPE (natural color);
4. Sheath: Black weather-resistant thermoplastic HDPE (green color).
Parameters
Exploitation temperature range,°C from -50 up to 50
Short-circuit temperature,°C 250
Bending radius 15D
Fire properties -
Operating conductor temperature,°C max +90
Cabling (inside/outside) outside
Installation temperature,°C -20
Initial modulus of elasticity of conductor, N/mm2 61000
Final modulus of elasticity of conductor, N/mm? 62500
Coefficient of linear expansion of conductor, 1/°C 23x10
Tensile strength, MPa min 295
Frequency, Hz 50
Rated voltage, kV 12/20
Wire sizes
Number of conductors 1
Minimum conductor size, mm 2 35
Maximum conductor size, mm2 240