AXCEL-F is a medium-voltage aluminum cable with pre-assembled XLPE-insulated conductors, ideal for distribution in buildings, open air, ducts, trays, ground, and wet environments. It's also suitable for plough cabling where mechanical damage is minimal.
 
The construction features water-tight aluminum conductors (EN 60228, Class 2), semi-conducting XLPE conductor and insulation screens, and XLPE insulation. Three insulated cores are pre-assembled; the WP variant includes swelling fillers. Inner coverings include semiconducting nonwoven or water-swellable tapes, with copper wires and tape applied helically as the screen. A plastic tape inner covering and an optional radial water barrier (WP) enhance durability, finished with a black PE sheath.
 
It operates from –60 °C to +50 °C, with a max conductor temperature of +90 °C and short-circuit tolerance up to +250 °C. Rated at 6/10 kV, tested at 21 kV, with a 12 × D bending radius. Sizes range from 10 to 300 mm².

0.00 KES

AXCEL-F / AXCEL-F (WP), HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
AXCEL-F / AXCEL-F (WP), HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with pre-assembled XLPE-insulated conductors. Suitable for
laying in buildings, in open air, in ground, in cable trays and ducts where mechanical damages are not expected,
in wet locations. Suitable for plough cabling.
Construction 1. Conductor: Aluminum acc. to EN 60228 (water tight). Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5, Assembly of cores: Three insulated cores are laid-up (pre-assembled). For WP - laid-up with interstice swelling fillers;
6. Inner covering: Semiconducting nonwoven tape. For WP - semiconducting water-swellable tape;
7. Screen: Copper wires and copper tape, applied helically;
8. Inner covering: Plastic tape. For WP - non-conducting water-swellable tape;
9. Radial water barrier: For WP - aluminum/plastic laminate tightly attached to outer sheath;
10. Cover: Weather-resistant black color PE.
Parameters
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 12d
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10
Cable Sizes
Number of conductors 3
Minimum conductor size, mm 10/10
Maximum conductor size, mm 300/25

info@belken-power.com