Additional product information
Power cables rated voltage 0.6/1 kV
AMCMK, MCMK, SFS 4880, HD 603, IEC 60502-1
Application Power cables suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 2 - RM (stranded,
round), Class 2 - SM (stranded, shaped), FLEX - for annealed cores;
2. Insulation: PVC (color code acc. to HD 603 clause 4);
3. Filler/inner covering: EPDM+PVC or PVC;
4. Screen: Copper wires and copper tape, applied helically;
5. Cover: PVC sheath (black color).
Parameters
Exploitation temperature range,°C from -30 to 50
4 Short-circuit temperature,°C 160
Bending radius 12D
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +70
Cabling (inside/outside) inside/outside
Installation temperature,°C =15
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 0,6/1
Cable sizes
Cu AI Cu AI Cu
Number of conductors 2+1 3+1 4+1
Minimum conductor size, mm? 6+6 16+10 6+6 16+10 6+6
Maximum conductor size, mm? 10+10 240+72 240+120 300+88 300+150