These medium-voltage aluminum cables are designed for power distribution in buildings, open air, ducts, trays, ground, and wet conditions. They are suitable for plough cabling and areas where mechanical damage is not expected.
 
The cables use water-tight aluminum conductors (EN 60228, Class 2), with XLPE insulation and semi-conducting XLPE conductor and insulation screens. Three insulated cores are pre-assembled, with WTL and WTR variants including swelling fillers. Inner coverings vary: standard uses nonwoven tape; WTL/WTR use water-swellable tape. A copper wire and tape screen, optional radial water barrier (WTR only), and weather-resistant black PE sheath complete the design.
 
They operate from –60 °C to +50 °C, with max conductor temperature of +90 °C, short-circuit limit of +250 °C, and 21 kV test voltage. Bending radius is 12 × D. Sizes range from 35 to 800 mm² (1-core) and 35 to 300 mm² (3-core).

0.00 KES

AHXCMK-WTC/PE AHXCMK-WTC/PE (WTL) AHXCMK-WTC/PE (WTR), HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
AHXCMK-WTC/PE AHXCMK-WTC/PE (WTL) AHXCMK-WTC/PE (WTR), HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with pre-assembled XLPE-insulated conductors. Suitable for
laying in buildings, in open air, in ground, in cable trays and ducts where mechanical damages are not expected,
in wet locations. Suitable for plough cabling.
Construction 1. Conductor: Aluminum acc. to EN 60228 (water tight). Class 2 - RMC (stranded, round, compacted),
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5, Assembly of cores: Three insulated cores are laid-up (pre-assembled). For WTL, WTR - laid-up with interstice swelling fillers;
6. Inner covering: Semiconducting nonwoven tape. For WTL, WTR - semiconducting water-swellable tape;
7. Screen: Copper wires and copper tape, applied helically;
8. Inner covering: Plastic tape. For WTL, WTR - non-conducting water-swellable tape;
9. Radial water barrier: For WTR - aluminum/plastic laminate tightly attached to outer sheath;
10. Cover: Weather-resistant black color PE.
Parameters
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 12d
Fire properties -
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10
Cable sizes 
Number of conductors 1  3
Minimum conductor size, mm 35/16 35/16
Maximum conductor size, mm 800/50 300/35

 