AHXAMK-WS is a medium-voltage aluminum cable with XLPE insulation, designed for power distribution in buildings, open air, ducts, ground, and wet environments. It features pre-assembled, individually sheathed cores laid around a steel messenger, making it ideal for overhead support or plough installation.
 
Constructed with water-tight Class 2 stranded aluminum conductors (EN 60228), semi-conducting XLPE screens, XLPE insulation, water-swellable tapes, and a radial water barrier of aluminum/plastic laminate, it is covered with a weather-resistant black PE sheath.
 
Operating in temperatures from –60°C to +50°C, withstanding short-circuits up to +250°C, and a maximum conductor temperature of +90°C, the cable supports 50 Hz systems and a test voltage of 21 kV. It allows installation down to –20°C with a minimum bending radius of 12 × D. Available sizes: 25/62 mm² to 300/62 mm².

0.00 KES

AHXAMK-WS, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
AHXAMK-WS, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with pre-assembled XLPE-insulated conductors, laid-up around
steel messenger. Suitable for laying in buildings, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected, in wet locations. Suitable for plough cabling.
Construction 1. Conductor: Aluminum acc. to EN 60228 (water tight). Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
7. Cover: Weather-resistant black color PE;
8. Assembly of cores: Individually sheathed cores are laid-up around a steel messenger.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 12d
Fire properties e
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10
Cable sizes 
Number of conductors 3
Minimum conductor size, mm 25/62
Maximum conductor size, mm 300/62

 