AHXAMK-WP is a medium-voltage XLPE-insulated power cable rated 18/30 kV, suitable for indoor/outdoor use, ground, ducts, trays, and wet locations—where mechanical damage is unlikely.
Construction: Class 2 aluminum conductors (EN 60228, water-tight), semi-conducting XLPE conductor screen, XLPE insulation and insulation screen, semiconducting water-swellable tape, radial water barrier of aluminum/plastic laminate, and black PE weather-resistant sheath.
Specifications: 3 conductors, sizes 50 mm² to 240 mm². Operating temp: up to +90 °C; short-circuit temp: +250 °C; installation temp: min -20 °C. Frequency: 50 Hz; test voltage: 63 kV; bending radius: 12×D. Operating range: -60 °C to +50 °C.

0.00 KES

AHXAMK-WP, HD 620-10F, IEC 60502-2

Additional product information

Power cables rated voltage 18/30 kV
AHXAMK-WP, HD 620-10F, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation. Suitable for laying in buildings, in open air, in
ground, in cable trays and ducts where mechanical damage is not expected, in wet locations.
Construction 1. Conductor: Aluminum acc. to EN 60228 (water tight). Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
7. Cover: Weather-resistant black color PE.
Parameters
Exploitation temperature range,°C from -60 up to 50
Short-circuit temperatur,e°C 250
Bending radius 12D
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C -20
Frequency, Hz 50
Testing voltage, kV 63
Rated voltage, kV 18/30
Cable sizes
Number of conductors 3
Minimum conductor size, mm 50
Maximum conductor size, mm 240