AHXAMK-WP is a medium-voltage aluminum power cable designed for distribution systems in buildings, open air, ducts, trays, ground, and wet environments. It's ideal where mechanical stress is minimal.
 
The cable consists of water-tight stranded aluminum conductors (EN 60228, Class 2), semi-conducting XLPE conductor and insulation screens, XLPE insulation, and a semiconducting water-swellable tape for inner covering. A radial water barrier of aluminum/plastic laminate and a tough black PE outer sheath provide protection and durability.
 
Key operating parameters include a temperature range from –60°C to +50°C, a maximum conductor temperature of +90°C, and a short-circuit limit of +250°C. It supports 50 Hz operation, 30 kV testing voltage, and has a bending radius of 12 × D. Available in sizes from 50 mm² to 300 mm² (3-core).

0.00 KES

AHXAMK-WP, HD 620-10F, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
AHXAMK-WP, HD 620-10F, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation. Suitable for laying in buildings, in open air, in
ground, in cable trays and ducts where mechanical damage is not expected, in wet locations.
Construction 1. Conductor: Aluminum acc. to EN 60228 (water tight). Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
7. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 up to 50
Short-circuit temperatur,e°C 250
Bending radius 12D
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C -20
Frequency, Hz 50
Testing voltage, kV 30
Rated voltage, kV 6/10
Cable sizes 
Number of conductors 3
Minimum conductor size, mm 50
Maximum conductor size, mm 300

info@belken-power.com