Medium voltage distribution cables designed for durability in wet or dry environments. These cables use XLPE insulation and are ideal for installation in buildings, open air, underground, ducts, and trays where mechanical damage is not expected. Also suitable for plough cabling. They are reliable for both indoor and outdoor applications, providing high thermal and mechanical stability, even in harsh climates.
 
The structure includes water-tight aluminum conductors (EN 60228, Class 2 - RMC), a semiconducting XLPE conductor screen and insulation layer, and a semiconducting insulation screen. A water-swellable tape forms the inner covering, surrounded by a radial water barrier of aluminum/plastic laminate and a weather-resistant black PE sheath.Three individually sheathed cores are laid around a bare earth conductor. Rated 12/20 kV; operating temp: +90°C; short-circuit temp: +250°C; install temp: -20°C; min bend radius:12×D; test voltage: 42 kV; frequency: 50 Hz. Sizes: 35/35 - 300/70 mm2

0.00 KES

AHXAMK-W, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12/20 kV
AHXAMK-W, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation. Suitable for laying in buildings, in open air,
in ground, in cable trays and ducts where mechanical damages are not expected, in wet locations. Suitable for
plough cabling.
Construction 1. Conductor: Aluminum acc. to EN 60228 (water tight). Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
7. Cover: Weather-resistant black color PE;
8. Assembly of cores: Individually sheathed cores are laid-up around a bare earth conductor.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 12d
Fire properties a
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 42
Rated voltage, kV 12/20
Cable sizes 
Number of conductors 3
Minimum conductor size, mm 35/35
Maximum conductor size, mm 300/70

 