Additional product information
Power cables rated voltage 64/110 kV
A2XS(FL)2Y, 2XS(FL)2Y, IEC 60840
Application For installation underground (in cable trenches), irrespective of corrosiveness of soil, if the cable is protected from
mechanical damage; for installation in water (in non-navigational water basins).
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE.
Parameters
Exploitation temperature range,°C from -60 up to 50
Short-circuit temperature,°C 250
Bending radius 15D
Fire properties :
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C -20
Frequency, Hz 50
Testing voltage, kV 160
Rated voltage, kV 64/110
Cable sizes
Al Cu
Number of conductors 1
Minimum conductor size, mm 185/95
Maximum conductor size, mm 1600/300
info@belken-power.com