Power cables rated voltage 3,6/6 kV
6-AYKCYDY, 6-CYKCYDY, CSN 347659, IEC 60502-2
Application Power cables for medium voltage distribution with PVC insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts, in areas with high risk of
mechanical damage.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - SM (stranded, shaped);
2. Insulation: PVC (color code acc. to HD 603);
3. Filler/inner covering: EPDM+PVC, PVC or plastic tape;
4. Screen: Copper wires and copper tape, applied helically;
5. Inner covering: PVC;
6. Armor: Galvanized round steel wires;
7. Cover: PVC sheath (black color).
Parameters
Exploitation temperature range,°C from -30 to +70
Short-circuit temperature,°C +160
Bending radius before 20 mm - 6d, over 20 before 40 mm - 12d, over 40 mm - 15d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +70
Cabling (inside/outside) inside/outside
Installation temperature,°C min -5
Frequency, Hz 50
Testing voltage, kV 125
Rated voltage, kV 3,6/6
Cable sizes
Al Cu
Number of conductors 3
Minimum conductor size, mm 25
Maximum conductor size, mm 240