Medium voltage power cables designed for distribution networks with XLPE insulation, concentric copper screen, and both longitudinal and radial water sealing. These cables are ideal for installation in buildings, power stations, in open air, underground, in cable trays, or ducts where mechanical damage is unlikely. They ensure reliable performance in indoor and outdoor applications.
 
The cable construction includes aluminum or copper conductors per EN 60228 (Class 2 - RMC), semi-conducting XLPE layers for the conductor and insulation screens, and XLPE insulation. A semiconducting water-swellable tape is used beneath a helically applied copper wire and tape screen. Another water-swellable layer and an aluminum/plastic radial barrier reinforce protection. Finished with a black weather-resistant PE sheath. Rated 20/35 kV, tested at 75 kV, max temp +90 °C, short-circuit +250 °C. Sizes: 50/16 to 500/35 mm², single-core.

0.00 KES

35-AXEKVCVE, 35-CXEKVCVE, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 20/35 kV
35-AXEKVCVE, 35-CXEKVCVE, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen, longitudinal and
radial sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 20d
Fire properties -
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 75
Rated voltage, kV 20/35
Cable sizes 
Al cu
Number of conductors 1
Minimum conductor size, mm 50/16
Maximum conductor size, mm 500/35