Medium voltage power cables with XLPE insulation and concentric copper screen, used in distribution networks. Suitable for installation in buildings, power stations, outdoors, underground, in ducts, trays, and other areas not subject to mechanical damage.
 
Constructed with aluminum or copper conductors (EN 60228, Class 2 - RMC), semi-conducting XLPE screens, XLPE insulation, and semiconducting nonwoven tape. Helically applied copper wires and tape form the screen, with a polyester inner covering and red PVC outer sheath. Rated 20/35 kV, operates from -50 °C to +50 °C, max conductor temp +90 °C, short-circuit temp +250 °C, install temp ≥ -15 °C, fire-rated EN 60332-1-2. Testing voltage: 75 kV, 50 Hz. Sizes: 50/16 to 500/35 mm², single-core.

0.00 KES

35-AXEKCY, 35-CXEKCY, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 20/35 kV
35-AXEKCY, 35-CXEKCY, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: PVC sheath (red color).
Parameters 
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -15
Frequency, Hz 50
Testing voltage, kV 75
Rated voltage, kV 20/35
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 50/16
Maximum conductor size, mm 500/35

 