These medium voltage cables are designed for distribution systems with XLPE insulation, concentric copper screen, and longitudinal water sealing. They are suitable for indoor, outdoor, underground, and cable tray installations where mechanical damage is not expected. Conductors are aluminum or copper (Class 2, per EN 60228), with semi-conducting XLPE screens around both the conductor and insulation layers.
 
Cables include water-swellable tapes for moisture protection, copper wires and tape for screening, and a dual outer sheath of weather-resistant PE and black PVC. They support operating temperatures up to +90°C, short-circuit conditions up to +250°C, and installation down to –15°C. Rated at 12.7/22 kV with a 50 kV test voltage and 50 Hz frequency, the bending radius is 15 times the cable diameter. Available in single-core, sizes range from 35 to 500 mm² (Al) and 16 to 35 mm² (Cu).

0.00 KES

22-AXEKVCEY, 22-CXEKVCEY, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12,7/22 kV
22-AXEKVCEY, 22-CXEKVCEY, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen and longitudinal
sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Non-conducting water-swellable tape;
8. Cover: Combined weather-resistant black color PE + PVC sheath (black color).
Parameters 
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -15
Frequency, Hz 50
Testing voltage, kV 50
Rated voltage, kV 12,7/22
Cable sizes
Al cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 500/35