These medium voltage power cables are designed for distribution applications in buildings, power stations, open air, underground, ducts, and trays, where mechanical damage is not expected. They feature XLPE insulation, a concentric copper screen, and longitudinal water sealing.
 
The conductor is aluminum (AXEKVCE) or copper (CXEKVCE), stranded and compacted to Class 2 (EN 60228). Layers include semi-conducting XLPE for conductor and insulation screening, XLPE insulation, and a semiconducting water-swellable inner covering. A copper wire and tape screen is applied helically, followed by a non-conducting water-swellable tape and a weather-resistant black PE sheath. The cables operate at up to +90 °C, tolerate short circuits up to +250 °C, and can be installed in temperatures down to –20 °C. They are rated 12.7/22 kV with a 50 kV test voltage for 50 Hz systems. Offered as single-core cables with aluminum (35–500 mm²) or copper (16–35 mm²) conductors.

0.00 KES

22-AXEKVCE, 22-CXEKVCE, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12,7/22 kV
22-AXEKVCE, 22-CXEKVCE, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen and longitudinal
sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4, Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Non-conducting water-swellable tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties .
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 50
Rated voltage, kV 12,7/22
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 500/35

 