These medium-voltage cables are designed for distribution in buildings, power stations, open air, underground, ducts, and trays where mechanical damage is not expected. They feature XLPE insulation and a concentric copper screen for enhanced electrical and thermal performance.
 
The construction includes aluminum (AXEKCY) or copper (CXEKCY) conductors (EN 60228, Class 2), semi-conducting XLPE conductor and insulation screens, and a semiconducting nonwoven tape. The screen consists of copper wires and tape, applied helically, followed by a polyester inner tape and red PVC sheath. Suitable for continuous operation up to +90 °C and short circuits up to +250 °C, with an installation minimum of –15 °C and operational range from –50 °C to +50 °C. Rated at 12.7/22 kV, test voltage 50 kV, fire-rated to EN 60332-1-2, for 50 Hz systems. Available in single-core, 35–500 mm² (Al) and 35 mm² max (Cu).

0.00 KES

22-AXEKCY, 22-CXEKCY, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12,7/22 kV
22-AXEKCY, 22-CXEKCY, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation:XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: PVC sheath (red color).
Parameters 
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -15
Frequency, Hz 50
Testing voltage, kV 50
Rated voltage, kV 12,7/22
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 500/35

 