These medium-voltage power cables are used for distribution systems in buildings, power stations, open air, underground, ducts, and trays where mechanical damage is unlikely. Featuring XLPE insulation and a concentric copper screen, they are suitable for a wide range of environments.
 
They consist of aluminum (AXEKCE) or copper (CXEKCE) conductors (EN 60228, Class 2), semi-conducting XLPE layers for conductor and insulation screening, and a semiconducting nonwoven inner covering. The copper screen is applied helically with wires and tape, followed by polyester tape and a weather-resistant black PE sheath. The cables operate at up to +90 °C with short-circuit tolerance to +250 °C, an installation minimum of –20 °C, and an ambient range of –60 °C to +50 °C. Rated at 12.7/22 kV, with a test voltage of 50 kV, for 50 Hz systems. Offered as single-core cables, from 35–500 mm² (Al) and 35 mm² max (Cu).

0.00 KES

22-AXEKCE, 22-CXEKCE, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 12,7/22 kV
22-AXEKCE, 22-CXEKCE, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties 
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 50
Rated voltage, kV 12,7/22
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 500/35

 

info@belken-power.com