The 10-AXEKVCVE (aluminum) and 10-CXEKVCVE (copper) cables are designed for medium-voltage power distribution with XLPE insulation, concentric copper screen, and combined longitudinal and radial water sealing. Suitable for installation in buildings, substations, open air, underground, ducts, and cable trays. These single-core cables feature Class 2 stranded, compacted conductors (EN 60228), semi-conducting XLPE conductor and insulation screens, water-swellable tapes, an aluminum/plastic laminate radial barrier, and a weather-resistant black PE sheath.
 
Rated at 6/10 kV and tested at 21 kV, these cables operate from –60°C to +50°C, tolerate short-circuit temperatures up to +250°C, and allow a conductor temperature up to +90°C. With a minimum installation temperature of –20°C and a bending radius of 20 × D, they are suitable for both indoor and outdoor applications at 50 Hz. Available sizes range from 35 mm² to 500 mm² (Al) and 16 mm² to 35 mm² (Cu).

0.00 KES

10-AXEKVCVE, 10-CXEKVCVE, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
10-AXEKVCVE, 10-CXEKVCVE, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen, longitudinal and
radial sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Semiconducting water-swellable tape;
8. Radial water barrier: Aluminum/plastic laminate tightly attached to outer sheath;
9. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 20d
Fire properties -
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 500/35

info@belken-power.com