The 10-AXEKVCEY (aluminum) and 10-CXEKVCEY (copper) cables are designed for medium-voltage power distribution with XLPE insulation, longitudinal water sealing, and a double-layered outer sheath of PE and PVC. They are suitable for installations in buildings, substations, open air, underground, ducts, and trays where mechanical damage is unlikely. These single-core cables include Class 2 stranded compacted conductors (EN 60228), semi-conducting XLPE layers, water-swellable tapes (both semiconducting and non-conducting), and a concentric copper screen.
 
Rated 6/10 kV and tested at 21 kV, these cables operate between –50°C and +50°C, handle short-circuit conditions up to +250°C, and support a conductor temperature of +90°C. They are flame-retardant (EN 60332-1-2), suitable for indoor and outdoor use, and operate at 50 Hz. With a bending radius of 15 × D and installation possible from –15°C, they are available in sizes from 35 mm² to 500 mm² (Al) and 16 mm² to 35 mm² (Cu).

0.00 KES

10-AXEKVCEY, 10-CXEKVCEY, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
10-AXEKVCEY, 10-CXEKVCEY, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen and longitudinal
sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Non-conducting water-swellable tape;
8. Cover: Combined: weather-resistant black color PE + PVC sheath (black color).
Parameters ez
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -15
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm? 35/16
Maximum conductor size, mm? 500/35

 

info@belken-power.com