The 10-AXEKVCE (aluminum) and 10-CXEKVCE (copper) cables are medium-voltage distribution cables with XLPE insulation, concentric copper screening, and longitudinal water sealing. Ideal for indoor and outdoor installations in buildings, substations, open air, underground, ducts, and trays where mechanical damage is not expected. These single-core cables are built with Class 2 stranded, compacted conductors (EN 60228), semi-conducting XLPE layers, semiconducting and non-conducting water-swellable tapes, a copper screen, and a durable black PE sheath.
 
Rated 6/10 kV and tested at 21 kV, these cables operate between –60°C and +50°C and can withstand short-circuit temperatures up to +250°C. They support a maximum conductor temperature of +90°C and are designed for 50 Hz systems. Minimum installation temperature is –20°C, and bending radius is 15 × D. Available in sizes from 35 mm² to 500 mm² (Al) and 16 mm² to 35 mm² (Cu).

0.00 KES

10-AXEKVCE, 10-CXEKVCE, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
10-AXEKVCE, 10-CXEKVCE, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation, concentric copper screen and longitudinal
sealing. Suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts where
mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting water-swellable tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Non-conducting water-swellable tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties cS
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10 Cable sizes anal 9€ /
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 500/35