The 10-AXEKCY (aluminum) and 10-CXEKCY (copper) are single-core, medium-voltage distribution cables with XLPE insulation and a concentric copper screen. Ideal for use in buildings, power stations, open air, underground, cable trays, and ducts where mechanical damage is unlikely. Constructed with Class 2 stranded, round, compacted conductors (EN 60228), they include semi-conducting XLPE conductor and insulation screens, semiconducting nonwoven tape, polyester tape, helically applied copper wires and tape, and a red PVC sheath.
 
Rated 6/10 kV and tested at 21 kV, these cables operate between –50°C and +50°C, withstand short-circuit temperatures up to +250°C, and support a conductor temperature up to +90°C. Designed for both indoor and outdoor installations at 50 Hz, they comply with EN 60332-1-2 fire standards. Bending radius is 15 × D, and installation is possible from –15°C. Available in sizes from 35 mm² to 500 mm² (Al) and 16 mm² to 35 mm² (Cu).

0.00 KES

10-AXEKCY, 10-CXEKCY, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
10-AXEKCY, 10-CXEKCY, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: PVC sheath (red color).
Parameters 
Exploitation temperature range,°C from -50 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -15
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10
Cable sizes 
Al Cu
Number of conductors 1
Minimum conductor size, mm? 35/16
Maximum conductor size, mm? 500/35