The 10-AXEKCE (aluminum) and 10-CXEKCE (copper) cables are designed for medium-voltage power distribution with XLPE insulation and a concentric copper screen. Ideal for installations in buildings, substations, open air, underground, ducts, and cable trays where mechanical damage is unlikely. Built with Class 2 stranded, compacted conductors (EN 60228), these single-core cables feature semi-conducting XLPE conductor and insulation screens, semiconducting nonwoven tape, polyester tape, helically applied copper screen, and a black weather-resistant PE sheath.
 
Rated at 6/10 kV and tested at 21 kV, they operate between –60°C and +50°C, withstanding short-circuit temperatures up to +250°C and supporting conductor temperatures up to +90°C. These cables are suitable for 50 Hz systems, indoor and outdoor use, with a minimum installation temperature of –20°C and a bending radius of 15 × D. Available in sizes from 35 mm² to 500 mm² (Al) and 16 mm² to 35 mm² (Cu).

0.00 KES

10-AXEKCE, 10-CXEKCE, PNE 347625, HD 620, IEC 60502-2

Additional product information

Power cables rated voltage 6/10 kV
10-AXEKCE, 10-CXEKCE, PNE 347625, HD 620, IEC 60502-2

Application Power cables for medium voltage distribution with XLPE insulation and concentric copper screen. Suitable for
laying in buildings, power stations, in open air, in ground, in cable trays and ducts where mechanical damages
are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228. Class 2 - RMC (stranded, round, compacted);
2. Conductor screen: Semi-conducting XLPE;
3. Insulation: XLPE;
4. Insulation screen: Semi-conducting XLPE;
5. Inner covering: Semiconducting nonwoven tape;
6. Screen: Copper wires and copper tape, applied helically;
7. Inner covering: Polyester tape;
8. Cover: Weather-resistant black color PE.
Parameters 
Exploitation temperature range,°C from -60 to +50
Short-circuit temperature,°C +250
Bending radius 15d
Fire properties 2
Operating conductor temperature,°C max +90
Cabling (inside/outside) inside/outside
Installation temperature,°C min -20
Frequency, Hz 50
Testing voltage, kV 21
Rated voltage, kV 6/10 Cable sizes es g /
Al Cu
Number of conductors 1
Minimum conductor size, mm 35/16
Maximum conductor size, mm 500/35

info@belken-power.com