Low-voltage power cables rated 0.6/1 kV, conforming to ČSN 34 7659, HD 603, and IEC 60502-1, designed for permanent installations in buildings, power stations, open air, underground, and in trays or ducts where mechanical damage is unlikely. These cables use aluminum (1-AYKY) or copper (1-CYKY) conductors per EN 60228, available in solid (Class 1 RE/SE) or stranded (Class 2 RM/SM) forms. They feature PVC insulation (HD 603 color code), EPDM or plastic tape fillers, and a black PVC sheath. Offered in configurations from 2 to 5 conductors, including 3+1 and 4+1, with sizes from 1.5 mm² to 300 mm². Suitable for temperatures from -50 °C to +50 °C, with a max conductor temperature of +70 °C and a short-circuit threshold of 160 °C. The cable maintains a bending radius of 12D, installs at ≥5 °C, operates at 50 Hz, and is tested at 4 kV. Fire-rated to EN 60332-1-2, these cables deliver dependable performance across varied power distribution setups.

0.00 KES

1-AYKY (-J, -O), 1-CYKY (-J, -O), ČSN 34 7659, HD 603, IEC 60502-1

Additional product information

Power cables rated voltage 0.6/1 kV
1-AYKY (-J, -O), 1-CYKY (-J, -0), CSN 347659, HD 603, IEC 60502-1

Application Power cables suitable for laying in buildings, power stations, in open air, in ground, in cable trays and ducts
where mechanical damages are not expected.
Construction 1. Conductor: Aluminum or copper acc. to EN 60228, Class 1 - RE (solid, round), Class 1 - SE (solid, shaped),
Class 2 - RM (stranded, round), Class 2 - SM (stranded, shaped);
2. Insulation: PVC (color code acc. HD 603 clause 4, -J - with Y/G core, -O - without Y/G core);
3. Filler/inner covering: EPDM or plastic tape;
4. Cover: PVC sheath (black color).
Parameters
Exploitation temperature range,°C from -50 to 50
Short-circuit temperature,°C 160
Bending radius 12D
Fire properties EN 60332-1-2
Operating conductor temperature,°C max +70
Cabling (inside/outside) inside/outside
Installation temperature,°C 5
Frequency, Hz 50
Testing voltage, kV 4
Rated voltage, kV 0,6/1
Cable sizes 
Al  | Cu | AI | Cu | AI | Cu | AI | Cu
Number of conductors 3 2 3 3+1 4 5
Minimum conductor size, mm 25 1,5 1,5 50+35 | 35+25 25 | 1,5 - 1,5
Maximum conductor size, mm 240 16 240 240+120 300 - 16

 